SA Heat Exchange designed and supplied multiple custom-configured gasketed plate heat exchangers for a specialist in data centre infrastructure and critical power solutions.
The heat exchangers were engineered to cool water from the cooling tower circuits using a 30% ethylene glycol solution from the chiller circuits. With individual thermal duties of up to 4.85 MW, the units were designed to reduce the cooling water temperature from 21°C to 16°C, accommodating flow rates in excess of 835 m³/h.
Three heat exchanger configurations were developed to accommodate the client’s thermal performance, installation footprint and operational requirements. The design incorporates Alloy 316 stainless steel plates and clip-on EPDM gaskets, providing enhanced corrosion resistance, efficient heat transfer and ease of maintenance.
Given the continuous cooling requirements of data centres, operational reliability, energy efficiency and serviceability were key design considerations. The expandable plate pack design also allows for additional cooling capacity to accommodate future infrastructure expansion.
The project highlights our expertise in advanced thermal design and high-capacity plate heat transfer solutions for mission-critical data centre infrastructure, where uninterrupted cooling, energy efficiency and long-term operational reliability are paramount.